| Just the basic FAQs
Drive-Alert Frequently Asked Questions
What should I do if I encounter false alarms (with no vehicle
passing the sensor)?
This can
occur suddenly, late at night or after a rainstorm. It is most
often a result of moisture making contact with exposed wires
through an accidental nick in the cable jacket. The control
panel may also have a problem.
First—remove the 3 sensor leads, (red, black and silver shield
wire). Wait approximately 1 minute, if no more alarms occur
after 1 minute, usually it is a problem with the sensor cable.
An ohmmeter test should be run in this case. Typically this
results from a cut/break in the cable outer jacket and
insulation of one or both inner conductors. Next, run a test of
the control panel itself (see below).
To run an
Ohmmeter test, first disconnect the cable from the control panel
terminals. Ohmmeter tests of the cable’s red and black leads
should show 800 ohms plus or minus 50 ohms. Then connect the
ohmmeter to the red lead and the silver shield lead-this should
read open circuit (very high resistance). Use the highest ohm
range the meter has. Note-some meters have a high reading of
just 2 million ohms-this may be too low if the problem is just
beginning or is initially 3-5 million ohms. Typically the meter
should have a 20 million ohms or higher range to catch initial
problems. Note-the problem can be aggravated by changing
resistance caused by moisture conductivity changes with
temperature.
For the
control panel test, disconnect the sensor for more than one
minute. If the alarm sounds continuously or intermittent alarms
occur without touching the circuit board, the control panel is
defective and needs repair. Momentary alarms can be induced by
touching BK and S terminals with moistened fingers. This test
may cause alarms that last 5 to 25 seconds. The control panel
should remain quiet thereafter. Do not touch the circuit board
after initiating an alarm. If no alarm occurs, check the blanker
LED at the back of the circuit board (note- blanker LED may
flash momentarily during the finger test). If ON continuously,
turn the blanker pot counterclockwise to turn off. If there is
no change and the LED remains on, the unit needs repair. The
blanker LED is usually ON for one minute when AC power is
initially applied to the control panel, and then is out at all
other times. If the power LED and/or blanker LED are out at all
times when the AC power is first applied, the unit needs repair.
Also, see next question for additional information.
What do R, BK and S stand for on the terminals?
R= Red
sensor wire
BK= Black sensor wire
S= Shield wire
What should I do if there are no alarms, but I can hear the internal
Drive-Alert relay clicking?
Check the
rear whistle switch; it should be ON for the Drive-Alert
internal alarm to sound. Also the internal 1 ampere glass fuse
should be checked (red LED adjacent to terminal strip is out if
fuse is open). The blown fuse problem occurs most often with
external alarm sounders connected to the NO and NEG terminals.
Replace the internal 1 ampere glass cartridge fuse if open. DO
NOT EXCEED FUSE RATING. Before replacing fuse, remove AC power
and external alarm connections. Place whistle switch in ON
position. Insert new fuse. Apply power and create alarm by
touching the BK and S terminals. The internal whistle should
sound and the red power LED alongside terminal strip should be
on. Reconnect the external alarms. If the fuse blows again,
check external alarm components and proper connection of the
wires to the external sounder.
Note-if
whistle switch is normally off and external sounders do not
operate but relay clicks, check external alarms. With rear
switch off external connections are between C and NO (the C and
NO terminals are closed each time the relay clicks).
What do I do if the vehicle alarm length is too short?
The alarm
duration is controlled by the Timer Adjust Pot. Turn the timer
pot adjustment counterclockwise to lengthen time. See the label
on the inside of the top cover for the timer-adjust-pot
location. Also check the blanker LED, if it is momentarily
flashing at the start of each alarm, adjust its pot slightly
counterclockwise (15-20 degrees).
What do I do if the vehicles on the street or road are tripping the
alarm?
Check the
sensor location; it should be 25 to 30 feet from the street.
Furthermore, if there is fast traffic (semi tractors) traveling
at high rates of speed, the sensor needs to be farther from the
road. Otherwise, reduce the sensitivity setting of the
Drive-Alert. Then, check if slow moving small vehicles still
activate Drive-Alert as it moves past sensor. If distance can
not be met, reduce sensitivity and/or move sensor closer to
moving vehicle. In some instances this can be addressed by
burying the sensor in the middle of the drive. Install a PVC
pipe to center of the drive, and slide sensor in pipe to the
middle of the drive. Then reduce the sensitivity setting.
May I use more than one sensor and protect more than one area?
Yes.
Whenever additional sensors are required there are two ways to
connect the sensors to the control panel – both sensors in
series connection or in a parallel connection. For the series
connection connect the sensor one red-lead to the R terminal,
the sensor one black-lead to the sensor two red-lead and the
sensor two black lead to the BK terminal. Tie both shield leads
to the S terminal. For the parallel connection tie both red
leads to the R terminal and both black leads to the BK terminal. All shield leads connect to the S terminal.
Whenever
more than 2 sensors are used, the series arrangement should be
used. Connect the sensor one red-lead to the R terminal, the
sensor one black lead to the sensor two red lead, and the sensor
two black lead to the next sensor red lead, etc. Connect the
last sensor black lead to the BK terminal. All shields connect
to the S terminal.
Using more
than 3 sensors will work, but with a gradual diminishing pickup.
This is the result of the sensor resistance and inductive
reactance reducing the signal as it passes through each sensor.
In a parallel connection, the sensor resistance of each in
parallel will reduce the available signal at the control panel
terminals. This effect has been rigorously tested for each
hookup and begins to show up when more than 3 sensors are used.
Why can’t I use the sensor without a control panel?
The sensor
is a passive device that contains no amplification. The detected
vehicle signal is very low in amplitude; thus, it will not
provide operation of any relay without a large amount of
amplification and signal shaping. The Mier Products’ control
panel removes extraneous signals as well as detects the various
waveforms that occur.
How do I increase the DA-505 timer power handling capability?
The
power handling capability of the DA-505 timer can be increased
by using the timer to operate a 25-30 ampere external relay with
its high current contacts. The relay coil (120VAC) can be driven
by the DA-505 timer and the external relay contacts used to
control the high power lights. Be sure to enclose the new relay
in a metal enclosure to prevent shock from the AC power.
What should I do if I have intermittent or non-operating DA-057
Powerflash Interface and DA-058 Chime modules (X-10)?
When using
the DA-500 and DA-057 Powerflash Interface transmitter and
DA-058 Chime module, verify you have a correct hookup (including
all DA-057 and DA-058 switch settings). If it’s a new hookup,
also verify correct wiring is in use, (resistor network to lower
control voltage to DA-057 approximately to 12-13VDC and wiring
is correct).
If
it’s an existing hookup that has been working properly, verify
the Drive-Alert control panel is functioning correctly. Then
press the Powerflash Interface transmitter TEST button (upper
left) to activate the remote chime. If there is no response,
move the chime to the same location as the DA-057 transmitter
and check once more. Verify the house and unit code settings are
the same on each module. If there is no response, then either
one or the other module is defective and needs replacement. If
the modules work at the same location, then try another outlet
in the chimes’ location. Also see suggestions for using a
Passive Phase Coupler under the following FAQ.
What should be done if, while using the Powerflash Interface modules
to operate a chime or lamp module, an intermittent operation occurs,
or one of the modules works in one outlet but does not respond in
other outlets?
In
this case, the signal strength on the house wiring may be the
cause. House wiring has two main 120 VAC circuits. Whenever a
Powerflash Interface transmitter is plugged into one AC outlet
and the associated chime or lamp module is plugged into an AC
outlet on the second circuit an insufficient signal may be
present and the module will not respond. At times, changes in
operation can be associated with a furnace, well-pump, or washer
operation. Move the inoperative module to the same location as
the transmitter to verify a weak signal is the problem. If this
is the case, the problem should be resolved with the use of a
Passive Phase Coupler which connects to both 120 VAC circuits in
the house service entrance panel. Follow the installation
instructions to place a Passive Phase Coupler in a service
entrance panel.
How do I test the DA-500 Control Panel for continuous and no alarms?
Disconnect
the sensor cable first and then run the ohmmeter test described
for false alarms. If the alarms stop the sensor cable is the
problem. If the alarms continue without touching the terminal
strip or circuit board for more than 1 minute, the control panel
needs repair. If no alarms occur and the control panel appears
to not function, then repair is required.
How do I use the DA-055 Chime System? What would cause the Chime to
be muffled?
The
DA-055 Chime System is an electronic chime that uses a relay
contact to activate the chime. The chime is a solenoid system
that uses a plunger to strike two chime bars. Check the mounting
of each bar. Muffled chime notes could be the result of chime
bars that have fallen off the grommet bar supports or the chime
is not upright. System operation can be checked by disconnecting
one wire from the DA-500 (C or NO terminals) then touching the
disconnected wire to the other wire. Two notes should sound. If
there is no chime note, then verify the chime power supply is
connected and 11 VAC is present internally on the two top
transformer wires. If the power is ok, then the chime may need
to be replaced. (NOTE: DO NOT operate the DA-500 control panel
with the whistle switch in ON position without first
disconnecting the two DA-055 wires). Place switch in OFF
position before connecting the two DA-055 wires back on the
terminal strip. Note-if a continuous alarm exists the chime will
not sound more than 2 notes. It will then remain silent.
What do I do if I am using the Drive-Alert for a Drive-up Window,
and I’m experiencing problems?
Intermittent operation can result if a sensor is located too far
from the vehicle. This can occur if the sensor is installed in
an overhead canopy that is 10 or more feet high. Also the sensor
must be located more than a vehicle length from the drive up
window. Small and/or low iron content vehicles moving slowly may
not produce sufficient signal change in the sensor to activate
the chime. Also the sensitivity setting should be checked. Turn
sensitivity pot setting clockwise to increase Drive-Alert
sensitivity. Placing a speed bump across the vehicle lane in
line with the sensor may help increase the vehicle signal. If
vehicles outside of the drive-up lane trigger the Drive-Alert,
reduce the sensitivity setting slightly.
How can I use a Home Alarm in conjunction with the Drive-Alert to
announce a vehicle’s presence?
The Mier
Products control panel can be connected to a home alarm system
requiring no voltage on the internal relay contacts (dry
contacts). The C, NC and NO terminals of the Drive-Alert control
panel can be used with home alarm systems by placing the whistle
switch on the back of the control panel in the OFF position.
This removes the internal voltage from the SPDT relay contacts
and also turns off the internal piezo whistle. DO NOT CONNECT
THE DRIVE-ALERT DRIVEWAY ALARM SYSTEMS TO OTHER ALARM SYSTEMS
WHICH ARE TIED TO THE POLICE OR OTHER SERVICES WITH FALSE ALARM
POLICIES.
How do I turn the Drive-Alert audible alarm off at selected times?
The
internal and external piezo whistles on the Drive-Alert can be
selectively turned off by placing the rear whistle switch in the
OFF position. A separate switch can be used by placing the
whistle switch in the off position and connecting an ON/OFF
switch between the C and plus 24 terminals. This will control
the application of Drive-Alert voltage on the C terminal. The
latter method will not allow the internal piezo whistle to
operate.
Can I use a remote whistle with the base model DA-500 Drive-Alert?
Yes, the
Mier Products DA-052 wall mount whistle can be used with the
DA-500 control panel to sound an alarm in any room (see the next
FAQ). However, it may be more cost efficient for you to use the
DA-503 or DA-504 models, which bring you more features (such as
remote chimes that can be placed in any receptacle in the house
and turning on lights) without the work and cost of hard-wiring.
Check out the DA-503 and DA-504 information on this website for
more details.
How can I connect an external piezo whistle to the Drive-Alert?
An
external piezo whistle rated 3-28 VDC can be connected to the
Drive-Alert. Two conductors with 22-24 gauge wire size is
adequate for this service. If it is desired to operate the
Drive-Alert without the internal piezo whistle, the rear whistle
switch should be placed in the OFF position and a jumper wire
connected from the front terminal strip +24 VDC position to the
C terminal.
Can I splice the sensor cable?
The
splicing of the sensor cable must be done with considerable care.
Moisture in a break in the cable jacket will result in false
alarms. The outer jacket of the cable is polyethylene material
that resists adherence of some sealants. Use of an ordinary
plastic tape will not produce a moisture proof splice. A
silicone based sealer may not be sufficient either. Mier
Products offers a tested and approved spliced kit, or we have
tested and approved cable lengths up to 2000 feet.
What if problems with the Drive-Alert persist?
If all the
tests above do not identify the problem, or control panel repair
is felt necessary, contact Mier Products for additional
assistance or send the control panel to the factory for testing
and repair.
|